MEC Home Page | Any Comments? Go to MEC Forum

The following is a set of modifications to the Model Energy Code which, taken together with that code, will constitute the Tucson / Pima County Sustainable Energy Standard, or Civano Energy Code. It was developed by the Tucson / Pima County Energy Codes Committee and has been reviewed by the Tucson / Pima County Building Code Committee.

This standard will be attached to the Memorandum of Understanding executed by the City of Tucson and the developers of the Community of Civano. It will serve as the statement of energy requirements for all buildings in Civano.

It is the intention of the Energy Codes Committee that this document will also serve as a voluntary sustainable energy standard for other buildings throughout Tucson and Pima County. It provides a quantifiable standard against which building plans can be measured to ensure that the finished buildings can be expected to enjoy substantially less energy usage than would have been the case under the Model Energy Code.


NOTE: The following sections have been changed since the previously published version, dated 3/14/98:

  • Section 102.4
  • Note to Table 503.35a
  • Section 603.4


SUSTAINABLE ENERGY STANDARD
4/22/98

The following modifications to the CABO Model Energy Code, 1995 Edition are deemed to be a sustainable standard:

(Editorial Note: This Energy Standard was reviewed by the Tucson/Pima County Building Code Committee and is regionally specific to the Tucson Metro area.)

Material to be added is shown in italics. Material to be deleted is shown as strikeout.

 

CHAPTER 1
ADMINISTRATION AND ENFORCEMENT

Section 101.4 Scope. Add a paragraph to read:
The calculated Target annual energy consumption of the building shell and mechanical system and domestic hot water heating shall be less than the energy required by the present Tucson/Pima County Model Energy Code by 50 percent.

Section 102.1.3 Add to first paragraph: , and there shall be a verification of proper installation before drywall installation and the completion of the "Insulation Installation Warranty" and signature` by a representative of the developer and builder.

Section 102.2 Maintenance Information. Delete the first two sentences.

Section 102.3 Change the first sentence to read: Whole-window assembly U-factor, solar heat gain coefficient, visible light transmittance and air leakage values of fenestration products ...

Table 102.3a Add the following notes at the end of the table:
The minimum design characteristics to qualify as a Thermal Break are:

  1. The material used as the thermal break must have a thermal conductivity of not more than 3.6 Btu/inch/hr/sq. ft./F, and;

  2. The thermal break must produce a gap not less than 0.210 inches, and;

  3. All metal members of the product exposed to interior and exterior air must incorporate a thermal break meeting the criteria in (a) and (b) above.

In addition, the product must be clearly labeled by the manufacturer that it qualifies as a thermally broken product. Non-metal products may include metal fasteners, hardware, and door thresholds.

For all dual glazed products, adjust the listed U-values as follows:

  1. Subtract 0.05 for spacers 7/16" or wider.
  2. Add 0.05 for products with dividers between panes if the spacer is less than 7/16" wide.
  3. Add 0.05 to any product with true divided lites (dividers through the panes).

Section 102.4 Equipment. Add a new subsection to read:
102.4 Equipment. Residential buildings constructed under the provisions of this standard shall be permitted to use refrigerated air conditioning systems selected under the guidelines of the Air Conditioning Contractors of America (ACCA) Manual J Procedures, Specifically Sections 7-27, 7-28 and 7-29 at outside conditions of 105 degrees F. and inside conditions of 75 degrees F. Other provisions of this standard notwithstanding, air conditioning equipment shall have a minimum SEER of 12 or a minimum EER of 10.

Evaporative cooling is encouraged for cooling or to reduce air conditioning requirements but may not be used as the method of compliance to this standard except for commercial buildings that use evaporative cooling as an economizer cycle on a refrigeration or air conditioning application. Duct leakage through the evaporative device must be minimized during air conditioning and heating modes of operation. Separate duct systems or whole house ductless ventilation is recommended.

Examples of water heating systems demonstrating compliance are listed here:

- Solar water heaters.
- Instant gas water heaters with electronic ignition.
- Heat pump electric water heaters.
- Heat recovery water heaters from air conditioning or other sources.
- Gas water heaters exceeding 90% efficiency (condensing types) .

Commercial buildings or domestic water heating systems which serve only hand sinks, a single mop sink or other applications which have low hot water demands on an annual basis may use any of the following:

- Instant electric water heaters.
- Point of use electric water heaters.
- Storage tank electric water heaters not exceeding 20 gallons in volume.

Section 104.1 General. Delete parenthesis around last sentence, delete the Footnote.
Add a sentence after the exception to read:
Plans and specifications shall show the method of utilizing "beneficial use of solar energy".


CHAPTER 2
DEFINITIONS

Section 201 Definitions. Revise as follows:
201.1 Application of Terms. Conditioned Floor Area:
Delete the words "The horizontal projection of", and capitalize the new first word "That".

201.1 Application of Terms. Positive Cooling Supply.
Insert including evaporative cooling systems, between "cooling" and "deliberately"

Add a new subsection:
201.1 Application of Terms. Civano. A Tucson Solar Village, a model sustainable community; a vision of the future where resource consumption is reduced through more efficient technologies, use of solar energy and lifestyles which promote greater harmony and balance with the natural environment; a community in the spirit of the "Civano" period, a golden era of the Hohokam culture which balanced natural resources and human needs; incorporates and demonstrates strategies for achieving more sustainable development.

201.1 Application of Terms. Sustainable Development. "Development that meets the needs of the present without compromising the ability of future generations to meet their needs." (UN World Commission on the Environment and Development)

201.1 Application of Terms. Beneficial Use of Solar Energy. The following devices/methods may be used to demonstrate compliance:

- Solar thermal or solar electric space heating systems.
- Trombe wall or clear view collectors for space heating.
- Solar Photovoltaic systems.
- Solar thermal/electric power generating systems, including stand-alone and grid connected parabolic trough and dish Stirling.
- Solar daylighting systems specifically designed to capture and redirect visible solar energy while controlling infrared energy (conventional skylights are specifically excluded) for at least one half of the non-bedroom space.
- Passive building heating for the winter through the use of optimum window shade structures and orientation.
- Solar water systems for domestic water heating or space heating.
- Solar pool or spa water heating.
- Solar oven that is built into the structure.
- Solar food dehydrator that is built into the structure.
- Solar water distiller attached to building.

201.1 Application of Terms. Power Density. The total connected power load of all components of a building system, including all auxiliary components and circuitry, without regard to the timing, scheduling, or control of their operation, in w/ft2 or Btuh/ft2.

201.1 Application of Terms. Site Energy. Energy, other than recovered energy, utilized for any purpose on the site.

Source energy consumption shall be determined by multiplying the site energy usage in kBtuh per square foot by the following factors:

Site Energy

Factor

Electric 3.10
Gas 1.11
Wood 1.00
Solar (amount of displaced electric or gas) 0.00


201.1 Application of Terms. SOLAR ENERGY SOURCE.
Revise to read:
Natural daylighting or thermal, chemical or electrical energy derived directly from conversion of incident solar radiation.

201.1 Application of Terms. Water-chilling Package of Absorption. Revise to read:
Water-chilling package, absorption.



CHAPTER 3
DESIGN CONDITIONS

Table 302.1 Exterior design conditions. Revise the table as follows:

Table 302.1
Exterior Design Conditions3

WINTER

DESIGN DRY BULB TEMP.

30 F

SUMMER

DESIGN DRY BULB TEMP.

104 F

 

DESIGN WET BULB TEMP.

66 F

DEGREE DAYS HEATING

 

7000

DEGREES NORTH LATITUDE

 

32

3 This table is not intended to be used for the purpose of system or equipment sizing.

Add a new section to read:

SECTION 304
WOOD-BURNING STOVES AND FIREPLACES

304.1 General. A wood-burning stove or fireplace shall be considered as providing the required space heating energy only when installed as backup energy for a solar-thermal collection system.

304.2 Wood-burning stoves. Wood-burning stoves shall be labeled to show compliance with the following U. S. Environmental Protection Agency (EPA) standards for particulate emissions during operation:

Stoves with catalytic elements 4.1 grams per hour
Stoves without catalytic elements 7.5 grams per hour

Catalytic stoves shall have an accessible, modular, replaceable catalyst element.

304.3 Fireplaces. Wood-burning fireplaces shall produce useful heat and be provided with a means of supplying 100% of the combustion air for operation from the outside, and shall limit particulate emissions to less than 7.5 grams per hour. All fireplaces shall be provided with a tight fitting glass door and a positive means of circulating the heated air in the occupied space.

Direct vent gas fireplaces shall have a minimum of 70% overall efficiency.


CHAPTER 4
RESIDENTIAL BUILDING DESIGN BY SYSTEMS ANALYSIS
AND DESIGN OF BUILDINGS UTILIZING
RENEWABLE ENERGY SOURCES

Section 402.1 Energy Analysis. Change the first paragraph to read:

402.1 Energy Analysis. Compliance with this chapter will require an analysis of the annual source energy usage as required in section 101.4, hereinafter called an annual energy analysis or shall not exceed the source energy usage shown in Table 402.1.

Table 402.1

Building

kBtu/Sq.Ft./yr.
(source consumption)

Sq. Ft. Range

Heating

Cooling

Total

<1000

5

22

27

1000 - 1399

4

18

22

1400 - 1799

4

16

20

1800 - 2199

4

15

19

>2200

4

14

18


402.1.1 Input Values for Group R Buildings. Add a sentence at the end of the first paragraph to read:
Domestic hot water energy use must be calculated separately from glazing systems, heat storage, thermal envelope and space conditioning equipment and must meet the energy reduction percentages of section 101.4.

Distribution System Loss Factor on page 12: Change the Outside factor for Cooling to read 0.75.

Add the following:
402.1.1.1 Thermal Mass. Designs utilizing thermal mass may be used provided the materials' volumetric heat capacity is between 18 minimum to 30 Btu/cu.ft. F (except water walls) and meet the values shown in Table 402.1., with walls without external insulation at least 12 inches minimum thickness or 8 hours time lag. External insulation can be used (R-9 to R-11) to reduce thickness of thermal mass to no less than 4". Surface area of uncovered thermal mass (in the direct sun zone) will be minimum 9 times the area of south glass, with 1ft2 of additional south glass for every 40 ft2 of mass located outside the direct sun zone (a simplified method of calculating thermal mass and south glass areas).

Table 402.1
Heat Storage Properties of Materials


Material


Specific Heat

(Btu/lb F)


Density

(lb/cu.ft.)

Volumetric
Heat Capacity
(Btu/cu.ft.-F)

Poured Concrete

0.16 -0.20

120 - 150

19.0 - 30.0

Clay Masonry

0.19 - 0.21

 

 

Molded Brick

 

120 - 130

19.0 - 27.3

Extruded Brick

 

125 - 135

23.8 - 28.4

Adobe

0.20 - 0.24

80 - 106

16.0 - 25.4

Concrete Masonry

0.19 - 0.22

 

 

CMU

 

80 - 140

15.2 - 30.8

Brick

 

115 - 140

21.9 - 30.8

Pavers

 

130 - 150

24.7 - 33.0

Water

1.0

62.4

62.4


402.1.1.2 Summer Ventilation. Thermal-mass buildings shall be provided with a means of venting to the outside at night during the months of May through October to avoid overheating. Operable windows totaling at least 20 percent of the total glazing area, located for effective cross-ventilation or ceiling fans or a whole-house fan sized to provide 10 air changes per hour may be used.

Section 402.4 Calculation Procedure. Operational Characteristics. Add a sentence to read:
The occupied mode shall be not less than 10 hours in a 24-hour period.

Section 402.5 Documentation. Delete the exception.


CHAPTER 5
RESIDENTIAL BUILDING DESIGN BY COMPONENT
PERFORMANCE APPROACH

Section 502.1 General. Add:
Thermal design parameters to be used in this chapter are found in Chapter 3, Section 302.1.

Section 502.1.2. Revise the second paragraph by placing a comma after "Masonry", and adding "earthen materials," between "Masonry" and "or".

Table No. 502.1.2c Delete the phrase " ,SUCH AS A LOGWALL " in the heading.

Section 502.2.1 Walls. Add a subsection to read:
502.2.1.2 Glazing. All glazing facing between 20 - 165 degrees or 195 - 340 degrees shall have a minimum summer shading coefficient of 0.39. All glazing facing between 165-195 degrees shall have a minimum summer shading coefficient of 0.5 or less. This may be accomplished by the use of overhangs, covered porches, tinted glazing, or other approved methods.

Table 502.2.1a Revise as follows

Table 502.2.1a1
HEATING AND COOLING CRITERIA

ELEMENT

MODE

TYPE A-1 BUILDINGS

TYPE A-2 BUILDINGS

 

 

Uo Uo
Walls Heating or cooling 0.11 0.17
Roof/Ceiling Heating or cooling 0.026 0.026
Floors over unheated spaces Heating or cooling 0.05 0.05
Heated slab on grade Heating R-Value 8 R-Value 8
Unheated slab on grade Heating R-Value 0 R-Value 0
Basement wall2 Heating or cooling U-Value 0.095 U-Value 0.095
Crawl space wall2,3 Heating or cooling U-Value 0.06 U-Value 0.06


1 Values are determined by using the graphs (Figure Nos. 1, 2, 3, 4, 5 and 6) contained in Chapter 8 using heating degree days as specified in Section 302.
2 Basement and crawl space wall U values shall be based on the wall components and surface air films. Adjacent soil shall not be considered in the determination of the U value.
3 Typical foundation wall insulation techniques can be found in Standard RS-20 listed in Chapter 8.

Add a new section 502.2.1.1 to read:
502.2.1.1 Software. Model Energy Code (MEC) software (DOS Version) called MEC check is available to verify compliance with this standard. It is available for download free from the Internet at:

http://www.energycodes.org/meccheck/mecdownload.html

To use the software:

Use DOS to modify the LOCATION file line 188 to read: Civano Tucson,7000,34892
Save the file and open the program.
Under state, select Arizona and under city, select Civano Tucson.
Select "Trade-offs" from the top bar and set HVAC Efficiencies for an air conditioner value of SEER 12.0 or better and Furnace AFUE to 80 or better. Corresponding heat pump values may be used.
Enter the building components and verify the building meets the MECcheck criteria.
Print the report with the check list (see Table 502.2.1.1 below) and submit for a permit.

Table 502.2.1.1
Check List to Accompany MEC Check Report when using Chapter 5

Section

Description

Check

502.2.1.2

Glazing facing between 195-340 and 20-165 degrees has a summer shade or shading coefficient of 0.39 or less. Glazing facing between 165-195 degrees has a summer shade or shading coefficient of 0.5 or less.

 

502.3

Air Leakage Warranty verifying maximum of 0.35 ACH.

 

503.2.4

Recessed lighting fixtures when installed in building envelope is constructed to accept only lamps with efficacy greater than 40 lumens/watt.

 

503.8.1

Duct Leakage Test passed before drywall and "Intermediate Verification and Warranty" form is signed.

 

101.4, 102.4

Water heater system demonstrating compliance.

 

504.2.1.1

Electric storage water heaters has a standby loss not to exceed
4 watts/ft2 of tank surface or 43 watts, whichever is greater.

 

504.5.1

Pools and spas utilize solar energy as the only water heating source.

 

504.5.4

Recirculating system (if used) is installed on hot water line with a timer and pipe insulation.

 

504.8

Low water use plumbing fixtures.

 


Section 502.2.4 Slab-on-grade floors. Delete in its entirety.

Section 502.3 Add the following sentence at the end:
An Air Leakage Warranty verifying a maximum of 0.35 ACH shall be provided to the home owner. A representative of the developer and/or builder will perform a blower door test after completion but before occupation of the residence. The representative will certify a maximum of 0.35 ACH based upon the results of the blower door test. An Air Leakage Warranty verifying a maximum of 0.35 ACH shall be provided to the homeowner.


Section 502.3.4 Recessed lighting fixtures. Revise the first paragraph to read:
503.2.4 Recessed Lighting Fixtures. When installed in the building envelope, recessed lighting fixtures shall be constructed so as to accept only lamps with efficacy greater than 40 lumens/watt, and meet one of the following requirements:

Section 503.2.1 Calculation Procedures. Add a sentence to read:
Equipment not covered by the tables in this section shall show the following maximum installed cooling power densities, including all auxiliaries:

less than 65,000 BTU/hr:

2.7 kW primary energy per 1000 sf at site

65,000 - 135,000 BTU/hr:

3.6 kW per 1000 sf

135,000 - 250,000 BTU/hr:

3.7 kW per 1000 sf

greater than 250,000 BTU/hr:

2.0 kW per 1000 sf

with energy intensity of mechanical cooling equipment calculated from EER ratings if entirely electric.

Table 503.35a Change the SEER values in the fourth column (Minimum Performance) from 10 and 9.7 to 12.0 and 10, respectively. Add the following note at the bottom of the table:
Note: Air-conditioning may be used selected under the guidelines of the Air Conditioning Contractors of America (ACCA)Manual J Procedures, Specifically Sections 7-27, 7-28 and 7-29 at outside conditions of 105 degrees F. and inside conditions of 75 degrees F.


Section 503.4 Add new sub-section to read:
503.4.3 Speed Reduction. An automatic method of speed reduction for pump and fan motors, or air or water flow reduction, during less than full system load conditions, which assures energy savings through motor power input reduction, shall be employed for any air system that exceeds a total system static pressure of 2.0 inches water gauge, and any water system that exceeds a total water system pressure equivalent to a 50 foot head of water.

Section 503.5 Balancing. Add a new second sentence to read: For structures with a floor area greater than 5000 square feet with forced-air climate control, balancing shall be performed, or included as part of a commissioning process from the design and construction phase. Certification and results of the balancing shall be submitted to the jurisdiction, the owner and the designer of the project.

Section 503.8.1 Delete in its entirety and add: All ducts shall be leak tested in accordance with this standard. The tested rate of air leakage is not to exceed 3% of conditioned floor area in CFM at 25 pascals (0.1 inches WC). A representative of the developer and/or builder will perform a field inspection and leakage test of the ductwork before drywall installation. The field representative will certify successful completion of this test.

Section 503.9 Piping Insulation. Delete exceptions 2 and 4, and renumber exception 3 to 2.

Section 504.2.1.1 Electric Water Heaters. Revise to read:
All Automatic electric storage water heaters shall have a standby loss not exceeding 4.0 watts/ft2 (43W/m2) of tank surface or 43 watts, whichever is greater, when tested in accordance with Standard RS-5 listed in Chapter 8 and calculated at a 30 Degrees F. temperature difference.

Section 504.5.1 Add the following at the beginning of the paragraph:
All recreational swimming pools and spas shall utilize solar energy as the only water heating source. Medical and rehabilitation pools smaller than 3,000 gallons water capacity shall use solar energy as the primary water heating source, with a new energy source permitted as backup.

Add a new Section 504.5.4:
Section 504.5.4 Recirculating Systems. Recirculating systems shall be provided with time clocks as required in Sec. 504.5.3, switches as required in Sec. 504.6, and pipe insulation as required in Sec. 504.7.

Section 504.8 Conservation of Hot Water. Delete in its entirety and add "Plumbing fixtures shall meet the following maximum usage requirements unless special requirements dictate otherwise:

- Water closets: 1.6 gallons per flush.
- Kitchen showers and lavatory faucets: 3 gallons per minute.
- Urinals: 1 gallon per flush.

Add a new section 506 to read:
Section 506. Energy Consumption - Other Than Electrical. In multifamily dwellings , provisions shall be made to determine the energy consumed by each tenant by separately metering individual dwelling units or tenant spaces.


CHAPTER 6
RESIDENTIAL BUILDING DESIGN BY ACCEPTABLE PRACTICE

Section 602.2.1 Walls. Add the following paragraph to read:

602.2.1.1 Wall Assemblies. Exterior walls shall be constructed to meet a minimum composite R-Value of 19 including air films. The following assemblies are deemed to meet this requirement:

  1. Nominal 2 x 6 wood-frame construction insulated with R-19 batts or applied blown-in process custom cavity filling insulation.
  2. Nominal 2 x 4 wood-frame construction insulated with R-13 batts or applied blown-in process custom cavity filling insulation and rigid insulation board on the exterior with an R-Value of not less than 3.2, with a nominal 4 inch brick veneer.
  3. Nominal 2 x 4 wood-frame construction insulated with R-13 batts or applied blown-in process custom cavity filling insulation and rigid insulation board on the exterior with an R-Value of not less than 6.0.
  4. Earthen material or solid masonry, at least 4 inches in thickness with insulation with an R-Value of not less than 9.0 applied to the exterior.
  5. Earthen material or solid masonry, at least 12 inches in thickness or 8 hours time lag.
  6. Straw bales at least 14 inches in thickness.
  7. Log or solid wood construction with an average thickness of 12 inches.
  8. Log or solid wood construction with an average thickness of 6 inches with nominal 2x4 frame construction insulated with R-13 batts or loose fill insulation on the inside.
  9. Structural insulated panels with a minimum R value of 25.

Add the following exceptions after the last paragraph:
Exceptions:

  1. Doors whose area and U-value are considered as glazing in section 602.2.1 shall be exempt.
  2. One exterior swinging door with a maximum area of 32 square feet may be installed for ornamental, security or architectural purposes and be exempt from these requirements.

Add new subsections to read:
602.2.1.1 Exterior Door Area. For doors containing at least 20 percent of the door area in glazing, the glazing area shall be subtracted from the door area for the purpose of determining the U-value of the door.

602.2.1.2 Exterior Door U-value. All exterior doors shall have maximum area weighted U-value not exceeding that prescribed in Table 102.3b.

602.2.1.3 Glazing. All glazing facing 20 - 165 degrees or 195 - 340 degrees shall have a minimum summer shade or shading coefficient of 0.39. All glazing facing between 165 - 195 degrees shall have a minimum summer shading coefficient of 0.5 or less. This may be accomplished by the use of overhangs, covered porches, tinted glazing or other approved methods. Whole-unit glazing maximum U-value shall be determined by the following equation or Table 602.2.1.3:

U = 5 / [(Glazing Percentage) - 5] or R = [(Glazing Percentage) - 5] / 5
where Glazing Percentage = 100 x (glazing area / floor area)

Table 602.2.1.3

Percent of floor area

Window R value

10

1.0

12

1.4

14

1.8

16

2.2

18

2.6

20

3.0

22

3.4

24

3.8

26

4.2

28

4.6

30

5.0


602.2.1.4 Summer Ventilation. Buildings utilizing thermal-mass (items 4 and 5, in section 602.2.1.1) shall be provided with a means of venting to the outside at night during the months of May through October to avoid overheating. Operable windows totaling at least 20 percent of the total glazing area, located for effective cross-ventilation and ceiling fans or a whole-house fan sized to provide 10 air changes per hour may be used.

Section 602.2.2 Roof/ceiling. Add a new subsection to read:

602.2.2.1 Roof/ceiling assemblies. Ceilings below ventilated attic spaces and single rafter vaulted ceilings shall be constructed to meet a minimum composite R-value of 38 including air films. The following assemblies are deemed to meet this requirement:

  1. Wood-frame assembly insulated with R-38 batts or loose-fill insulation.
  2. Earthen material or solid masonry at least 12 inches in thickness with glass fiber or foam insulation with an R-Value of not less than 22 applied to the interior.
  3. Earthen material or solid masonry at least 24 inches in thickness with glass fiber or foam insulation with an R-Value of not less than 11 applied to the interior.
  4. Earthen material or solid masonry at least 36 inches in thickness
  5. Straw bales at least 14 inches in thickness.
  6. Structural insulated panels with an R value of at least 38.

Section 602.2.4 Slab-on-grade Floors. Delete 2nd paragraph and insert the following sentence:
At least 25 percent of the floor area in the living space shall be without carpet or an equivalent area of internally exposed mass.

Section 602.3 Add the following sentence at the end:
An Air Leakage Warranty verifying a maximum of 0.35 ACH shall be provided to the home owner per Section 502.3.

Section 603.2 HVAC Equipment Requirements. Change to read:
. . . efficiency and power density requirements of section 503.2, 503.3 and 503.8.1.

Table 603.5 Minimum Pipe Insulation. Revise by changing the numbers 1 1/2 to 1/2 in the third and fourth columns on the line "CHILLED WATER".

Section 603.6 Add a new section to read:
603.6 Space Cooling. Buildings constructed under the provisions of this standard shall be permitted to use refrigerated air conditioning systems selected under the guidelines of the Air Conditioning Contractors of America (ACCA)Manual J Procedures, Specifically Sections 7-27, 7-28 and 7-29 at outside conditions of 105 degrees F. and inside conditions of 78 degrees F. Other provisions of this standard notwithstanding, air conditioning equipment shall have a minimum SEER of 12 or a minimum EER of 10. System sizing shall be determined by an analysis consistent with industry standards.

Section 603.7 Add a new subsection to read:
603.7 Mechanical Equipment and Water Heater Efficiency. The efficiency of water heating and mechanical equipment shall be in accordance with sections 101.4, 102.4 and 503 of this standard.

Check List when using Chapter 6

Section

Description

Check

102.1.3

"Insulation Installation Warranty" completed and signed.

 

102.4

Minimum of 600 ft2/ton.

 

104.1

A method of utilizing solar energy (may overlap with 504.2).

 

503.2.4

Recessed lighting fixtures when installed in building envelope are constructed to accept only lamps with efficacy greater than 40 lumens/watt.

 

503.8.1

Duct Leakage Test passed before drywall and "Intermediate Verification and Warranty" form is signed.

 

101.4, 102.4

Water heater system demonstrating compliance.

 

504.2.1.1

Electric storage water heaters has a standby loss not to exceed 4 watts/ft2 of tank surface or 43 watts, whichever is greater.

 

504.5.1

Pools and spas utilize solar energy as the only water heating source.

 

504.5.4

Recirculating system (if used) is installed on hot water line with a timer and pipe insulation.

 

504.8

Low water use plumbing fixtures conform with UPC.

 

602.2.1.3

Glazing facing between 195-340 & 20-165 degrees has a summer shade or shading coefficient of 0.39 or less.

Glazing facing between 195-165 degrees has a summer shade or shading coefficient of 0.5 or less.

 

602.2.1

Wall assembly from table 602.2.1.1

 

602.2.1.2

All exterior doors but one (maximum of 32 ft2) to be R-5.

 

602.2.1.3

Minimum window U value as per Table 602.2.1.3

 

602.2.1.4

Buildings utilizing thermal mass walls have minimum 20% operable windows or ceiling fans or a whole house fan (10 ACH).

 

602.2.2.1

Minimum composite R value of 38 for roof/ceiling.

 

602.2.4

Minimum of 25% of floor area without carpet or equivalent area of other internally exposed mass.

 

602.3

"Air Leakage Warranty" verifying maximum of 0.35 ACH.

 

SECTION 604
SERVICE WATER HEATING

Section 604.1.2.3 Swimming Pools and Spas. Add the following at the beginning of the first paragraph:
All recreational swimming pools and spas shall utilize solar energy as the only water heating source. Medical and rehabilitation pools smaller than 3,000 gallons water capacity shall use solar energy as the primary water heating source, with a new energy source permitted as backup. When permitted, spa and Ppool . . . . . remainder unchanged.

Section 604.2 Water Heaters, Storage Tanks and Boilers. Add a sentence to read:
Shall comply with Section 101.4 and 102.4 of this standard.

Section 604.4 Conservation of Hot Water. Delete in its entirety and add: "Plumbing fixtures shall meet the following maximum usage requirements unless special requirements dictate otherwise:

- Water closets: 1.6 gallons per flush.
- Kitchen showers and lavatory faucets: 3 gallons per minute.
- Urinals: 1 gallon per flush.


CHAPTER 7
BUILDING DESIGN FOR ALL BUILDINGS OTHER THAN

RESIDENTIAL BUILDINGS

Section 702.1 Basic Requirements. Revise to read as follows:

702.1 Basic Requirements. Building designs shall meet the requirements of Section 101.4 and 102.4 of this standard as well as the requirements of Sections 5.4, 6.4, 7.4, 8.4, 9.4, 10.4, 11.4 and 12.4 in Standard RS-22 listed in Chapter 8.

Section 702.2 Additional Requirements. Add the following before the first exception:
Buildings otherwise meeting the requirements of Chapter 4, 5 or 6 of this standard may employ the following performance requirement substitutions of Standard RS-22, listed in Chapter 8.
Remainder unchanged.

Add a new section to read:


SECTION 703
ELECTRICAL REQUIREMENTS

703.1 Lighting Power Budget. The maximum lighting power density (LPD) for any building may be calculated by either the Complete Building Method or the Area Category Method, according to the following table:

Table 703.1
Complete Building Method

Building Type

Max. Lighting Power Density (W/sf)

 

 

General commercial or industrial work buildings

0.8

Grocery stores

1.2

Industrial or commercial storage buildings

0.5

Medical buildings and clinics

1.0

Office buildings

1.0

Religious worship, auditorium/convention centers

1.3

Restaurants

1.0

Retail and wholesale stores

1.3

Schools

1.2

Theaters

1.0

All others

0.5

Area Category Method

Area Type

Max. Lighting Power Density (W/sf)

 

 

Auditorium

1.3

Bank/financial institutions

1.2

Classrooms

1.3

Convention/conference/meeting centers

1.0

Corridors, restrooms, support areas

0.5

Dining

0.8

Exhibit

1.5

General commercial and industrial work

0.8

Grocery

1.3

Hotel function

1.5

Industrial and commercial storage

0.4

Kitchen

1.5

Lobbies: Hotel lobby

1.5

Main entry lobby

1.0

Malls, arcades, and atria

0.8

Medical and clinical care

1.2

Office

1.0

Precision commercial and/or industrial work

1.3

Religious worship

1.4

Retail sales, wholesale showrooms

1.4

Theaters: Motion picture

0.7

Performance

1.0

For any building greater than 5,000 square feet in area, and for all non-residential buildings, the following shall apply:

Lighting design shall comply with current IESNA guidelines and application notes, with selection of the median illuminance as the target optimum, not the minimum. In all areas designated higher than IESNA category C, specified illuminance shall be on task, with ambient illuminance generally task/3. LPD shall in no case exceed the values in Table 703.1. In all areas, lighting targets shall be achieved by the most energy efficient technology which meets the following requirements:

  • CRI greater than 80 for work areas, greater than 75 for all areas.
  • Color Temperature less than 3600 K, except in retail display, excluding tasklights

Technologies include but are not limited to:

  • Incorporation of natural daylight, and daylight-supplementing artificial light
  • Area lighting by high-CRI straight tube fluorescent with specular reflectorized interior luminaire. For applications which do not involve frequent switching, use fully electronic instant start 4-lamp parallel-circuit ballasts. Daylight-dimming via photocell sensor/controller.
  • Task lighting by 13 watt lamps (or smaller), with laterally offset placement so as not to cause direct or veiling glare
  • Conference rooms to have continuous architectural-dimming (to10%) fluorescent luminaries in place of incandescent can downlights, or else can lights controlled by center-off double throw switch which prevents simultaneous operation of area lights and downlights.
  • Reflectorized technologies for interior luminaries.
  • Areas with visible daylight may use continuous-dimming photocell-controlled variable light output devices except those controlled by non-defeatable occupancy sensors. Daylighting contribution to be considered in calculation of IESNA target illuminance.

Prohibited technologies include:

  • Tungsten filament incandescent except quartz-halogen
  • T12 fluorescent
  • VHO and SHO lamps
  • Mercury vapor lamps
  • U-shaped lamps (except CFLs <20W)
  • Small-cell paracube grates and large cell paracube fixtures where the lamp is not centered into the cell
  • Magnetic fluorescent ballasts
  • Series-circuit ballasts

Occupancy Sensors shall be specified and installed in accordance with EPA Green Lights guidelines, with control technology appropriate to the application. Areas with video display terminals shall be primarily illuminated by task lighting, use of overhead luminaries in each space to be evaluated for Visual Comfort Probability. Visual acuity factors are to be treated as minus weighting factors.


Back to Top | MEC Home Page